    The GLS-SIM is a compact interface device designed to allow Crestron Green Light® sensors to be connected directly to a Cresnet control network. Cresnet® is the communications backbone for Crestron sensors, dimmers, keypads, touchpanels, shade controllers, thermostats, and many other devices. This flexible 4-wire bus provides data communications and 24 Volts DC power for all of the devices on the Cresnet network. The GLS-SIM installs easily at the sensor location, mounting conveniently inside the electrical box or exposed above the ceiling. Wiring connections to the network and sensor are facilitated using miniature screw terminals.
    The GLS-SIM is compatible with Crestron GLS-series sensors, as well as with most 24 Volt-powered sensors from any manufacturer. Up to 1A @ 24VDC power is available
    [1]
    to support multiple sensors in parallel. The GLS-SIM actually includes two sensing inputs, each capable of sensing a contact closure, logic level, or 0-10V analog signal. When used with a Crestron IPAC or iLux® system, setup is simplified using onboard DIP switches to select the sensor type (i.e. occupancy, photocell, partition, etc.) and operating mode (i.e. normally-open or normally-closed).
    Key Features
    Provides Cresnet® connectivity for Crestron GLS-series and third-party sensors
    Works with occupancy sensors, photocells, partition sensors, and more
    Provides 24 Volts DC to power one or more sensors
    Includes 2 independent sensing inputs
    Supports contact-closure, DC logic, and 0-10V analog signals
    Onboard DIP switches simplify setup for use with IPAC and iLux® systems
    Allows fully-programmable operation as part of any Crestron system
    Compact module fits in an electrical box behind the sensor
    Miniature screw terminals facilitate reliable wiring connections
    Connectors
    NET
    (1) 4-pin 5mm detachable terminal block;
    Cresnet slave port, connects to Cresnet control network
    SENSOR
    (1) 4-pin 3.5mm detachable terminal block;
    Sensor input comprised of 24VDC power output and (2) digital or analog input ports (referenced to GND);
    Digital Input: Rated for 0-24 Volts DC, input impedance 20k ohms, logic threshold 1.25 Volts DC;
    Analog Input: Rated for 0-10 Volts DC, protected to 24 Volts DC maximum, input impedance 20k ohms;
    Programmable 5 Volts, 2k ohms pull-up resistor per pin;
    Maximum Power Load: 1 Amp @ 24 Volts DC
    [1]
    Controls
    ID CODE
    (2) Rotary DIP Switches;
    Used for manually setting Cresnet ID;
    ‘00’ setting enables touch-settable ID (TSID)
    MODE
    (1) 4-position DIP switch;
    Sets sensor type and operating mode for use with IPAC and CLS-C6 systems
    SETUP
    (1) miniature pushbutton, used for touch-settable ID (TSID)
    LED Indicators
    PWR
    (1) green LED, indicates 24 Volts DC power supplied from Cresnet control network
    NET
    (1) yellow LED, indicates communication with Cresnet system
    SETUP
    (1) red LED, used for touch-settable ID (TSID)
    Environmental
    Temperature
    32° to 104°F (0° to 40°C)
    Humidity
    0% to 95% RH (non-condensing)
    Power Requirements
    Cresnet Power Usage
    1 Watt (0.04 Amps @ 24 VDC) (Does not include power draw of attached devices.)
    Dimensions
    Height
    2.00 in (51 mm)
    Width
    2.00 in (51 mm)
    Depth
    0.86 in (22 mm)
    Weight
    2 oz (46 g)